Model |
HLG-320H-12 |
HLG-320H-15 |
HLG-320H-24 |
Output |
DC VOLTAGE |
12V |
15V |
24V |
CURRENT ADJ. RANGE |
11-22A |
9.5-19A |
16.67-3.34A |
RATED POWER |
264W |
285W |
320.16W |
VOLTAGE ADJ. RANGE |
10.8-13.5V |
13.5-17V |
21-26V |
Input |
Voltage Range |
90-305VAC 127-431V DC |
Frequency Range |
47-63Hz |
POWER FACTOR |
PF>0.98/115VAC, PF>0.95/230VAC, PF>0.94/277VAC at full load (Please refer to "Power Factor Characteristic" curve) |
Efficiency(Typ.)(230Vac) |
91% |
92.5% |
94% |
Efficiency(Typ.)(227Vac) |
91.5% |
93% |
94.5% |
AC CURRENT (Typ.) |
3.5A / 115VAC 1.65A / 230VAC 1.45A / 277VAC |
INRUSH CURRENT(Typ.) |
COLD START 75A/230VAC |
LEAKAGE CURRENT |
<0.75mA / 277VAC |
PROTECTION |
OVER LOAD |
95~ 108% |
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
SHORT CIRCUIT |
Hiccup mode, recovers automatically after fault condition is removed. |
OVER VOLTAGE |
14-17V |
17.5-21V |
27-33V |
Protection type :Shut down O/P voltage, re-power on to recover |
OVER TEMPERATURE |
100 ℃ up or less10 ℃ (RTH2) |
|
Protection type : Shut down and latch off o/p voltage, re-power on to recover |
Environment |
WORKING TEMP. |
-40 ~ +70 ℃(Refer to output load derating curve) |
WORKING HUMIDITY |
20 ~ 95% RH non-condensing |
SAFETY |
SAFETY STANDARDS |
UL8750, CSA C22.2 No. 250.0-08, EN61347-1, EN61347-2-13 independent (except for HLG-320H C type),IP65 or IP67, J61347-1, J61347-2-13 approved ; design refer to UL60950-1, TUV EN60950-1 |
WITHSTAND VOLTAGE |
I/P-O/P:3.75KVAC I/P-FG:1.88KVAC O/P-FG:0.5KVAC |
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC / 25 / 70% RH |
EMC EMISSION |
Compliance to EN55015, EN55022 (CISPR22) Class B, EN61000-3-2 Class C ( 50% load) ; EN61000-3-3 |
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61547, EN55024, light industry level (surge 4KV), criteria A |
Others |
MTBF |
157.1K hrs min. MIL-HDBK-217F (25℃ ) |
DIMENSION |
252*90*43.8mm (L*W*H) |
PACKING |
1.88Kg; 8pcs/16Kg/0.83CUFT |
Note |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a
12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to .EMI testing of component power supplies..
(as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details. |